313-6CF03 - CPUs | CPUs STEP7 programmable, class C

Order no.

313-6CF03

TypeCPU 313SC/DPM

General information

Note-
FeaturesSPEED7 technology,

16 x DI, 16 x DO,

64 kB work memory,

Memory extension (max 512 kB),

PROFIBUS-DP master / PtP (switchable)
SPEED-Bus-

Technical data power supply

Power supply (rated value)DC 24 V
Power supply (permitted range)DC 20.4...28.8 V
Reverse polarity protection
Current consumption (no-load operation)200 mA
Current consumption (rated value)900 mA
Inrush current11 A

Technical data digital inputs

Number of inputs16
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)70 mA
Rated valueDC 24 V
Input voltage for signal "0"DC 0...5 V
Input voltage for signal "1"DC 15...28.8 V
Input voltage hysterese-
Frequency range-
Input resistance-
Input current for signal "1"6 mA
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current1.5 mA
Input delay of "0" to "1"0.1 / 0.35 ms
Input delay of "1" to "0"0.1 / 0.35 ms
Number of simultaneously utilizable inputs horizontal configuration-
Number of simultaneously utilizable inputs vertical configuration-
Input characteristic curveIEC 61131, type 1
Initial data size2 Byte

Technical data digital outputs

Number of outputs16
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)100 mA
Total current per group, horizontal configuration, 40°C3 A
Total current per group, horizontal configuration, 60°C2 A
Total current per group, vertical configuration2 A
Output voltage signal "1" at min. currentL+ (-0.8 V)
Output voltage signal "1" at max. current-
Output current at signal "1", rated value0.5 A
Output current, permitted range to 40°C5 mA to 0.6 A
Output current, permitted range to 60°C5 mA to 0.6 A
Output current at signal "0" max. (residual current)0.5 mA
Output delay of "0" to "1"-
Output delay of "1" to "0"-
Minimum load current-
Lamp load5 W
Parallel switching of outputs for redundant control of a loadpossible
Parallel switching of outputs for increased powernot possible
Actuation of digital input
Switching frequency with resistive loadmax. 2.5 kHz
Switching frequency with inductive loadmax. 0.5 Hz
Switching frequency on lamp loadmax. 2.5 kHz
Internal limitation of inductive shut-off voltageL+ (-52 V)
Short-circuit protection of outputyes, electronic
Trigger level1 A
Number of operating cycle of relay outputs-
Switching capacity of contacts-
Output data size2 Byte

Technical data analog inputs

Number of inputs-
Cable length, shielded-
Rated load voltage-
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage inputs-
Min. input resistance (voltage range)-
Input voltage ranges-
Operational limit of voltage ranges-
Basic error limit voltage ranges-
Current inputs-
Min. input resistance (current range)-
Input current ranges-
Operational limit of current ranges-
Basic error limit current ranges-
Resistance inputs-
Resistance ranges-
Operational limit of resistor ranges-
Basic error limit-
Resistance thermometer inputs-
Resistance thermometer ranges-
Operational limit of resistance thermometer ranges-
Basic error limit thermoresistor ranges-
Thermocouple inputs-
Thermocouple ranges-
Operational limit of thermocouple ranges-
Basic error limit thermoelement ranges-
Programmable temperature compensation-
External temperature compensation-
Internal temperature compensation-
Resolution in bit-
Measurement principle-
Basic conversion time-
Noise suppression for frequency-
Initial data size-

Technical data analog outputs

Number of outputs-
Cable length, shielded-
Rated load voltage-
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage output short-circuit protection-
Voltage outputs-
Min. load resistance (voltage range)-
Max. capacitive load (current range)-
Output voltage ranges-
Operational limit of voltage ranges-
Basic error limit voltage ranges-
Current outputs-
Max. in load resistance (current range)-
Max. inductive load (current range)-
Output current ranges-
Operational limit of current ranges-
Basic error limit current ranges-
Settling time for ohmic load-
Settling time for capacitive load-
Settling time for inductive load-
Resolution in bit-
Conversion time-
Substitute value can be applied-
Output data size-

Technical data Counters

Number of counters3
Counterwidth32 Bit
maximum input frequency30 kHz
Maximum count frequency30 kHz
Mode incremental encoder
Mode pulse / direction
Mode pulse
Mode frequency counter-
Mode period measurement-
Gate input available
Latch input available
Reset input available-
Counter output available

Load and working memory

Load memory, integrated512 KB
Load memory, maximum512 KB
Work memory, integrated64 KB
Work memory, maximal512 KB
Memory divided in 50% program / 50% data
Memory card slotMMC-Card with max. 1 GB

Hardware config

Racks, max.4
Modules per rack, max.8
Number of integrated DP master1
Number of DP master via CP4
Operable function modules8
Operable communication modules PtP8
Operable communication modules LAN8

Status information, alarms, diagnostics

Status displayyes
Interruptsyes
Process alarmyes
Diagnostic interruptyes
Diagnostic functionsno
Diagnostics information read-outpossible
Supply voltage displaygreen LED
Group error displayred SF LED
Channel error displayred LED per group

Command processing times

Bit instructions, min.0.02 µs
Word instruction, min.0.02 µs
Double integer arithmetic, min.0.02 µs
Floating-point arithmetic, min.0.12 µs

Timers/Counters and their retentive characteristics

Number of S7 counters512
Number of S7 times512

Data range and retentive characteristic

Number of flags8192 Byte
Number of data blocks4095
Max. data blocks size64 KB
Max. local data size per execution level510 Byte

Blocks

Number of OBs15
Number of FBs2048
Number of FCs2048
Maximum nesting depth per priority class8
Maximum nesting depth additional within an error OB4

Time

Real-time clock buffered
Clock buffered period (min.)6 W
Accuracy (max. deviation per day)10 s
Number of operating hours counter8
Clock synchronization
Synchronization via MPIMaster/Slave
Synchronization via Ethernet (NTP)no

Address areas (I/O)

Input I/O address area1024 Byte
Output I/O address area1024 Byte
Input process image maximal128 Byte
Output process image maximal128 Byte
Digital inputs8064
Digital outputs8064
Digital inputs central1008
Digital outputs central1008
Integrated digital inputs16
Integrated digital outputs16
Analog inputs503
Analog outputs503
Analog inputs, central248
Analog outputs, central248
Integrated analog inputs0
Integrated analog outputs0

Communication functions

PG/OP channel
Global data communication
Number of GD circuits, max.4
Size of GD packets, max22 Byte
S7 basic communication
S7 basic communication, user data per job76 Byte
S7 communication
S7 communication as server
S7 communication as client-
S7 communication, user data per job160 Byte
Number of connections, max.32

Functionality Sub-D interfaces

TypeX2
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated-
MPI
MP²I (MPI/RS232)-
DP master-
DP slave-
Point-to-point interface-

TypeX3
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated
MPI-
MP²I (MPI/RS232)-
DP master
DP slave
Point-to-point interface
CAN-

Functionality PROFIBUS Master

PG/OP channel
Routing
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Equidistance support-
Isochronous mode-
SYNC/FREEZE
Activation/deactivation of DP slaves
Direct data exchange (slave-to-slave communication)-
DPV1-
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Number of DP slaves, max.32
Address range inputs, max.1 KB
Address range outputs, max.1 KB
User data inputs per slave, max.244 Byte
User data outputs per slave, max.244 Byte

Functionality PROFIBUS Slave

PG/OP channel
Routing
S7 communication
S7 communication as server
S7 communication as client-
Direct data exchange (slave-to-slave communication)-
DPV1-
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Automatic detection of transmission speed-
Transfer memory inputs, max.244 Byte
Transfer memory outputs, max.244 Byte
Address areas, max.32
User data per address area, max.32 Byte

Point-to-point communication

PtP communication
Interface isolated
RS232 interface-
RS422 interface-
RS485 interface
ConnectorSub-D, 9-pin, female
Transmission speed, min.150 bit/s
Transmission speed, max.115.5 kbit/s
Cable length, max.500 m

Point-to-point protocol

ASCII protocol
STX/ETX protocol
3964(R) protocol
RK512 protocol-
USS Master protocol
Modbus Master protocol
Modbus Slave protocol-
Special protocolls-

Functionality RJ45 interfaces

TypeX5
Type of interfaceEthernet 10/100 MBit
ConnectorRJ45
Electrically isolated
PG/OP channel
Productive connections-

Mechanical data

Dimensions (WxHxD)80 mm x 125 mm x 120 mm
Weight420 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL508 certificationyes